⚡ Electrical & Energy
Circuit Breaker Sizing Calculator
Determine the correct breaker amp rating and wire gauge for any electrical load. NEC compliant with 80% continuous load rule and voltage drop check.
Frequently Asked Questions
How do I determine breaker size?▼
I = Watts ÷ Volts. For continuous loads: multiply by 1.25 (NEC 80% rule). Round up to next standard size (15, 20, 25, 30, 40, 50, 60A). Then match wire gauge to breaker per NEC Table 310.16.
What is the NEC 80% rule?▼
Continuous loads (3+ hours) can't exceed 80% of breaker rating. So: breaker = load amps × 1.25. A 24A continuous load needs 30A breaker (24 × 1.25 = 30). Prevents overheating.
What wire size for each breaker?▼
Copper wire (60°C): 14 AWG=15A, 12 AWG=20A, 10 AWG=30A, 8 AWG=40A, 6 AWG=50-55A, 4 AWG=70A, 3 AWG=80A, 2 AWG=95A, 1 AWG=110A, 1/0=125A. Upsize for long runs (voltage drop).
What breaker for common appliances?▼
Dryer: 30A/240V (10 AWG). Oven: 40-50A/240V (8-6 AWG). Water heater: 30A/240V. AC: 30-60A/240V. EV charger: 40-60A/240V. Microwave: 20A/120V. General outlets: 15-20A/120V.
What is voltage drop?▼
Voltage loss along wire length. NEC recommends max 3% for branch circuits. Matters for long runs: at 100ft, 20A on 12 AWG loses 3.2% at 120V. Fix by using larger wire gauge. Our calculator checks this automatically.
Single vs double pole breaker?▼
Single pole: 120V circuits (lights, outlets). Double pole: 240V circuits (dryer, oven, AC, water heater, EV charger). Double pole trips both legs simultaneously for safety.
How to calculate panel load?▼
Sum all loads with NEC demand factors: first 10,000VA at 100%, rest at 40%. Add largest of AC or heat (not both). Divide total by 240V. Most homes need 200A service. Consult an electrician for panel upgrades.