Wire Size Calculator — Free AWG, Ampacity & Voltage Drop Wire Gauge Selector 2026 | AllInOneTools
🔌 Electrical & Energy

Wire Size Calculator

Select the correct AWG wire gauge based on amperage, voltage, distance, and conductor material. Includes NEC ampacity tables, voltage drop calculation, and breaker matching.

Circuit Requirements
Amps
feet
📋
Wire Specifications
📊
NEC Ampacity Reference
📝 Step-by-Step Selection
💡

Wire Size Calculator: The Complete Guide to Selecting the Correct AWG Gauge

Selecting the correct wire size is critical for safety, code compliance, and performance. Undersized wire overheats — causing insulation damage, circuit breaker nuisance tripping, and fire risk. Oversized wire wastes money. The right wire size balances ampacity (safe current-carrying capacity) and voltage drop (acceptable power loss over distance) per NEC requirements.

Wire Selection Formula

Step 1 — Ampacity: Select wire with NEC ampacity ≥ load amps
Step 2 — Voltage Drop: VD = (2 × L × I × R/ft) for 1-phase
      VD = (√3 × L × I × R/ft) for 3-phase
Step 3 — VD% = (VD ÷ System Voltage) × 100
Step 4 — If VD% > max allowed, upsize wire
Step 5 — Use the LARGER of ampacity-based and VD-based sizes
Worked Example — 20A Kitchen Circuit, 75 ft
Load: 20A, 120V single-phase, copper, 75 ft one-way
Ampacity: 12 AWG (NEC breaker max 20A on 12 AWG) ✓
12 AWG resistance: 1.93 mΩ/ft
VD = 2 × 75 × 20 × 0.00193 = 5.79V (4.8%)
4.8% exceeds 3% limit → upsize to 10 AWG
10 AWG: VD = 2 × 75 × 20 × 0.00122 = 3.66V (3.05%)
Still borderline → use 10 AWG copper (30A rated)

NEC Ampacity Table (75°C Copper)

AWGAmpacity (Cu)Ampacity (Al)Breaker (Cu)Resistance (mΩ/ft)
1420A15A3.07
1225A20A20A1.93
1035A30A30A1.21
850A40A40A0.764
665A50A55A0.491
485A65A70A0.308
3100A75A85A0.245
2115A90A95A0.194
1130A100A110A0.154
1/0150A120A125A0.122
2/0175A135A150A0.0967
3/0200A155A175A0.0766
4/0230A180A200A0.0608
Pro Tip — Always Use the Larger Wire
When ampacity and voltage drop calculations suggest different wire sizes, always use the larger (lower AWG number). For long runs (over 50 ft at 120V), voltage drop usually requires upsizing beyond the minimum ampacity requirement. The extra cost of larger wire is minimal compared to the performance and safety benefit. Also consider future load growth — installing slightly larger wire now is much cheaper than re-wiring later.
Safety — Wire Sizing is Code-Critical
Undersized wire is a leading cause of residential electrical fires. Always follow NEC 310.16 for ampacity and NEC 210.19/215.2 for voltage drop recommendations. The NEC breaker-to-wire relationship in 240.4(D) is absolute: 14 AWG = 15A max breaker, 12 AWG = 20A, 10 AWG = 30A. Never install a larger breaker to "fix" tripping — the breaker protects the wire. If a breaker trips frequently, the circuit is overloaded and needs to be split or the wire upsized.

Frequently Asked Questions

What size wire do I need?
Depends on amps, distance, and voltage. Common: 15A = 14 AWG, 20A = 12 AWG, 30A = 10 AWG, 50A = 6 AWG, 100A = 1 AWG (copper). For long runs, upsize for voltage drop. Our calculator checks both ampacity and voltage drop automatically.
What is AWG?
American Wire Gauge — standard measuring system. Smaller number = thicker wire = more capacity. 14 AWG is thinner than 12, which is thinner than 10. Below 1 AWG: 1/0, 2/0, 3/0, 4/0. Each AWG step changes area by ~50%.
What is voltage drop and why does it matter?
Voltage loss over wire distance due to resistance. NEC recommends max 3% for branch circuits, 5% total. Too much drop causes dim lights, motor overheating, and equipment malfunction. Longer runs need larger wire to keep drop acceptable.
Copper or aluminum wire?
Copper: better conductor, smaller size, more expensive. Aluminum: cheaper, requires 1-2 sizes larger, needs anti-oxidant on connections. Aluminum is common for service entrance and large feeders (40A+). Never mix without listed connectors. Use AL-rated devices only.
What is the 80% rule?
Continuous loads (3+ hours) can't exceed 80% of wire/breaker rating per NEC. A 20A breaker on continuous load = 16A max. Size wire for 125% of continuous load. This prevents overheating from sustained current.
What size wire for 200 amp service?
Copper: 2/0 AWG. Aluminum: 4/0 AWG. Ground: 4 AWG copper. Most residential 200A services use aluminum SE cable (much cheaper). Conduit: 2" minimum for copper, 2.5" for aluminum.
How far can I run 12 gauge wire?
At 120V, 20A load, 3% max drop: about 50 feet one-way. At 15A: about 65 feet. At 10A: about 100 feet. Beyond these distances, upsize to 10 AWG. At 240V, distances double because the percentage drop is halved. Use our calculator for exact distances.